Designation
Service
Rise
Pressures
PSI
Temp F
(Dead Band)
(Amps)
Approvals
Enclosure
Notes
8757-J400-449-24VDC
Air
SPDT1
0-20" wc
3,225 (6)
160
1-2" wc
1
FM, UL, CE
4X
1.6
8757-J400-451-24VDC
Air
SPDT1
0-80" wc
3,225 (6)
160
1-3" wc
1
FM, UL, CE
4X
1,6
8757-H400-453-24VDC
Air
SPDT1
0-20 psi
20,225 (6)
160
0.05-0.2 psi
1
FM, UL, CE
4X
1,6
8757-H400-454-24VDC
Air
SPDT1
0-30 psi
30,225 (6)
160
0.05-0.3 psi
1
FM, UL, CE
4X
1,6
8757-DG-2I-24VDC
Gas, Air
SPDT1
0.2-2.4" wc
8.5
176
0.08-0.12" wc
0.1
FM, UL
IP65
1,3
8757-DG-4I-24VDC
Gas, Air
SPDT1
0.4-4.0" wc
8.5
176
0.1-0.16" wc
0.1
FM, UL
IP65
1,3
8757-DG-20I-24VDC
Gas, Air
SPDT1
1-20" wc
8.5
176
0.31-0.59" wc
0.1
FM, UL
IP65
1,3
8757-DG-60I-24VDC
Gas, Air
SPDT1
12-60" wc
8.5
176
1.17-1.95" wc
0.1
FM, UL
IP65
1,3
8757-DG-200I-24VDC
Gas, Air
SPDT1
40-200" wc
8.5
176
3.12-6.63" wc
0.1
FM, UL
IP65
1,3
8757-GAO-A4/4/2 GOLD
Gas, Air
SPDT1
0.16-1.2"wc
7
140
0.12"wc
20mA
FM, UL, CSA
4
1, 3
8757-GAO-A4/4/3 GOLD
Gas, Air
SPDT1
0.4-4.0"wc
7
140
0.2"wc
20mA
FM, UL, CSA
4
1, 3
8757-GAO-A4/4/5 GOLD
Gas, Air
SPDT1
2-20"wc
7
140
0.4"wc
20mA
FM, UL, CSA
4
1, 3
8757-GAO-A4/4/6 GOLD
Gas, Air
SPDT1
12-60"wc
7
140
1.2"wc
20mA
FM, UL, CSA
4
1, 3
8757-GAO-A4/4/8 GOLD
Gas, Air
SPDT1
40-200"wc
14
140
4.0"wc
20mA
FM, UL, CSA
4
1, 3
8757-GML-A4/4/4 SILVER
Gas, Air
SPDT1
1-20"wc
7
140
0.4"wc
20mA
FM, UL, CSA
4
1, 3, 7
8757-GML-A4/4/6 SILVER
Gas, Air
SPDT1
12-60"wc
7
140
1.2"wc
20mA
FM, UL, CSA
4
1, 3, 7
8757-GMH-A4/4/6 SILVER
Gas, Air
SPDT1
12-60"wc
7
140
1.2"wc
20mA
FM, UL, CSA
4
1, 3, 7
8757-12-20I-24VDC
Gas, Air, Oil
SPDT1
-20-20" wc
75, 100 (6)
203
0.5-3.5: wc
1 res, 0.5 ind
CE, ANSI/ISA
4X, Cls I, II
1,5,6,9
12.27.01, UL, cUL
Div. I, II
8757-D4-30I-24VDC
Gas, Air, Oil
SPDT1
4.5-30" wc
40,160 (6)
150
1.5-2.5" wc
6
FM, UL, CE, CRN, CSA
4X
1,5,6,8,9
8757-12-50I-24VDC
Gas, Air, Oil
SPDT1
2-50" wc
75, 100 (6)
203
0.5-5" wc
1 res, 0.5 ind
CE, ANSI/ISA
4X, Cls I, II
1,5,6,9
12.27.01, UL, cUL
Div. I, 11
8757-D4-60I-24VDC
Gas, Air Oil
SPDT1
9-60" wc
40,160 (6)
150
1.5-3.5" wc
6
FM, UL, CE, CRN, CSA
4X
1,5,6,8,9
8757-D4-100I-24VDC
Gas, Air, Oil
SPDT1
15-100" wc
40,160 (6)
150
2.5-5.5" wc
6
FM, UL, CE, CRN, CSA
4X
1,5,6,8,9
8757-D4-150I-24VDC
Gas, Air, Oil
SPDT1
22.5-150" wc
40,160 (6)
150
4.5-8.5" wc
6
FM, UL, CE, CRN, CSA
4X
1,5,6,8,9
8757-12-200I-24VDC
Gas, Air, Oil
SPDT1
10-200" wc
75, 100 (6)
203
1-10" wc
1 res, 0.5 ind
CE, ANSI/ISA
4X, Cls I, II
1,5,6,9
12.27.01, UL, cUL
Div. I, II
8757-12-15P-24VDC
Gas, Air, Oil
SPDT1
1-15 psi
300,500 (6)
203
0.5-2.0 psi
1 res, 0.5 ind
CE,ANSI/ISA
4X, Cls I,II
1,5,6,9
12.27.01, UL, cUL
Div. I, II
8757-B4-15P-24VDC
Gas, Air, Oil
SPDT1
2.25-15 psi
120,500 (6)
150
0.5-1.5 psi
6
FM, UL, CE, CRN, CSA
4X
1,5,6,8,9
8757-B4-30P-24VDC
Gas, Air, Oil
SPDT1
4.5-30 psi
120,500 (6)
150
0.5-1.5 psi
6
FM, UL, CE, CRN, CSA
4X
1,5,6,8,9
8757-12-50P-24VDC
Gas, Air, Oil
SPDT1
3-50 psi
300,500 (6)
203
0.5-4 psi
1 res, 0.5 ind
CE,ANSI/ISA
4X, Cls I,II
1,5,6,9
12.27.01, UL, cUL
Div. I, II
8757-B4-60P-24VDC
Gas, Air, Oil
SPDT1
9-60 psi
120,500 (6)
150
1.0-3.5 psi
6
FM, UL, CE, CRN, CSA
4X
1,5,6,8,9
8757-12-100P-24VDC
Gas, Air, Oil
SPDT1
5-100 psi
300,500 (6)
203
1.0-8 psi
1 res, 0.5 ind
CE,ANSI/ISA
4X, Cls I,II
1,5,6,9
12.27.01, UL, cUL
Div. I, II
8757-B4-100P-24VDC
Gas, Air, Oil
SPDT1
15-100 psi
400,1000 (6)
150
1.5-5 psi
6
FM, UL, CE, CRN, CSA
4X
1,5,6,8,9
8757-B4-200P-24VDC
Gas, Air, Oil
SPDT1
30-200 psi
400,1000 (6)
150
5-13 psi
6
FM, UL, CE, CRN, CSA
4X
1,5,6,8,9
Switch
Rating
24Vdc
Switch
Action
Press.
Range of
Operating
Max
Static
Max
Ambient
Diff erential
Pressure
NOTES:
1. SPDT (Single Pole Double Throw) action means the switch makes one circuit and breaks another.
2. DPDT (Double Pole Double Throw) action means the switch makes two circuits and breaks two circuits.
3. These pressure switches must be mounted level and where they are relatively free from vibration.
4. A siphon (ordered seperately) must always be connected between the pressure switch and the line when used with steam to act as a themal
buff er.
Specify R830-6699 for 180° siphon, R830-6698 for a 90° siphon.
5. When used with pre-heated oil, a siphon loop must always be connected between the pressure switch and main pipe to act as a themal buff er.
6. The fi rst pressure rating under heading "Max Static psi" is the max allowable pressure that can be applied without the need for recalibration. The
second pressure rating is the proof pressure, which is defi ned as the max pressure to which the switch may be subjected to causing no perma-
nent damage, however recalibration must be performed.
7. Manual Reset required.
8. These switches have a
¼
" vent which must be piped to an approved location.
9. These switches do not require a conduit seal to meet 4.1.3.2 of NFPA 86 2019.
Bulletin 8757
page 5
Static Pressure 24VDC | Pressure Switches
For use with safety PLC systems