WARNING:
Situations dangerous to personnel and property may exist with the operation and maintenance of any combustion equipment. The presence of fuels, oxidants, hot and cold combustion products, hot
surfaces, electrical power in control and ignition circuits, etc., are inherent with any combustion application. Components in combustion systems may exceed 160°F (71°C) surface temperatures and present hot
surface contact hazard. Fives North American Combustion, Inc. suggests the use of combustion systems that are in compliance with all Safety Codes, Standards, Regulations and Directives; and care in operation.
"H" AND "W" TYPE BOOT AND SNAP-LOCK REPLACEMENT INSTRUCTIONS
"N" TYPE BOOT AND SNAP-LOCK REPLACEMENT INSTRUCTIONS
"C" TYPE
¼
" Ø SNAP-LOCK IGNITION TRANSFORMER CLIP REPLACEMENT INSTRUCTIONS
½
"
Snap-lock
R360-5055
"W" Boot
R360-5052
"H" Boot
R360-5054
1. Strip
5⁄8
" insulation off wire
2. Bend wire back as shown above
3. Crimp snap-lock on insulation
4. Insert snap-lock into boot as shown
1. Strip
½
" insulation off wire
2. Insert wire into boot as shown above
3. Secure clip with slotted screwdriver (clockwise to tighten)
Sheet 4085
Page 5
"N" Boot
R840-5821
Screwdriver
½
"
1. Strip
5⁄8
" insulation off wire
2. Bend wire back
½
" as shown
3. Crimp snap-lock clip on insulation, as shown
4. Heat shrink plastic sleeve over clip and wire
Ignition Transformer Clip
R840-4998
Plastic Sleeve